To set the appropriate operating mode for correcting the power
factor of generators, press the key: the word will appear. If,
on the contrary, you wish to enable the C.T. direction auto-
adjustment function
(in the case of traditional power factor correction of loads) press
the key: the word will appear to confirm the selection
.
This command reinstates all the default parameters and returns
the controller to the initial starting up condition; after this
operation, reset the controller by following the directions in
chapter 7 for (after
setting the parameter, the controller always starts the
procedure for acquiring banks, see chap. 7.3 - Page 63).
Press + to access the setup menu and press the key
repeatedly until the set logic (1:1:1, 1:2:2, 1:2:4) is displayed; to
reset the controller, keep pressed for 5 seconds.
The letters “ ” will be displayed in turn with the default setting
“”.
The parameter can be changed using the or key and
confirming with the key. The possible choices are:
= no reset will be carried out.
= the parameters will be reset; during this phase the
controller will switch off all the steps and the digits will
appear for a few seconds with all LEDs illuminated
The REGO controller features a device for signaling overvoltage
and power factor correction failures as well as alarms which are
activated when an overtemperature protection trips or in the event
of excessive harmonic distortion and voltage drops or mains dips.
When a protection trips, the LED will light up and the NC
contact will close to remotely signal the alarm status. With the
exception of the device for signaling power factor correction
failures and overvoltage, the protections will cause the capacitor
banks to be switched off.
This signal is activated when the system power factor remains
below the set value for more than two consecutive hours
(reentries of up to 1 minute are allowed) with all the capacitor
banks switched on. This signaling function is not active in the
manual mode. When a power factor correction failure is signaled:
the initials will be displayed in turn with and the
last value measured (these digits will also be separated by )
Ex.
the LED situated on the front panel of the controller
will light up.
the alarm relay contact connected to the controller terminal
block will open.
After 30 minutes all these actions will be cleared and the controller
will automatically resume operation (auto-reset status ),
though the incident will continue to be signaled via the display,
which will show in turn with and the last value
measured.
To clear the display press .
On
OFF
12.9 TOTAL RESETTING OF SETUP PARAMETERS
POWERING UP FOR THE FIRST TIME
IL
DATA
ALARM/RESET
CLr
no
DATA
no
yes
8.8.8.
13) SIGNALS AND ALARMS
ALARM
13.1 SIGNALING OF POWER FACTOR CORRECTION
FAILURE
A.L.A. C.O.S.
...
ALARM
A.r.
A.L.A. C.O.S.
ALARM/RESET
13.2 OVERVOLTAGE SIGNAL
A.L.A. U.F.F.
...
ALARM
UFF
A.r.
A.L.A. U.F.F.
ALARM/RESET
13.3 OVERTEMPERATURE PROTECTION
A.L.A. .C..
...
ALARM
rapid
disconnection
A.r.
A.L.A. .C..
ALARM/RESET
13.4 PROTECTION AGAINST EXCESSIVE HARMONIC
DISTORTION
A.L.A. t.h.d.
...
ALARM
t.h.d.
rapid
disconnection
This signal is activated when the controller measures a supply
voltage exceeding the maximum allowed by the transformer (230
+19%; 400 +19%) for longer than 30 seconds.
This protection is active even if no capacitor bank is currently
switched on. When this alarm is triggered:
the initials will be displayed in turn with and the
last value measured (these digits will also be separated by )
Ex.
the LED situated on the front panel of the controller
will light up.
the alarm relay contact connected to the controller terminal
block will open.
the number shown by the alarm counter will increase by
one.
After 30 minutes all these actions will be cleared and the
controller will automatically resume operation (auto-reset
status ), though the incident will continue to be signaled via
the display, which will show in turn with and
the last value measured. To clear the display press
.
This protection will trip if the temperature around the controller
exceeds 700C for at least 15 seconds.
When this alarm is triggered:
the initials will be displayed in turn with “° and the
last temperature read (these digits will also be separated by ).
Ex.
the LED situated on the front panel of the controller
will light up.
the alarm relay contact connected to the controller terminal
block will open.
the controller will activate the procedure for
of all steps and go into a standby status (in
this status the controller will not work).
After 30 minutes all these actions will be cleared and the
controller will automatically resume operation (auto-reset status
), though the incident will continue to be signaled via the
display, which will show “ ” in turn with “° ” and the last
value measured.
To clear the display press .
This protection is also active in the manual mode and even if no
capacitors are switched on.
This protection will trip when the rate of current harmonic
distortion may pose a hazard to the power factor correction
capacitors.
When this alarm is triggered:
the initials will be displayed in turn with and the
measured Crest Factor (these digits will also be separated by ).
Ex.
the LED situated on the front panel of the controller
will light up.
the alarm relay contact connected to the controller terminal
block will open.
the number shown by the alarm counter will increase by
one.
the controller will activate the procedure for
of all steps and go into a standby status (in
this status the controller will not work).